REGULATION OF ALTERNATORS
When an alternator is subjected to a varying load,
the voltage at the armature terminals varies to certain extent, the amount of
this variation determines the regulation of the machine.Phasor diagram of an alternator at
lagging power factor is as follows.
Regulation
is found by the following expression
Where
V
is the terminal voltage and E0 is
the induced voltage. E0
is estimated by the following methods.
1)
EMF Method
2)
MMF Method
3)
ZPF Method
4)
ASA Method
5)
Slip Test
1) EMF method
(Synchronous impedance method)
Conduct
tests to find I) OCC (up to 125% of rated voltage) II) SCC
(for rated current) III) Armature resistance (per phase)
V = rated phase voltage
Isc = short circuit current corresponding to the field current
producing the rated voltage
Synchronous
impedance per phase,
For
any load current I
and phase angle Φ, find E0
as the vector sum of V,
IRa and IXs
For lagging
power factor
For unity power
factor
2) MMF method (Ampere turns method)
Conduct
tests to find I) OCC (up to 125% of rated voltage) II) SCC (for rated current)
STEPS:
1.
By suitable tests plot OCC and SCC
2.
From the OCC find the field current If1
to produce rated voltage, V.
3.
From SCC find the magnitude of field current
If2 to produce the required
armature current.
4.
Draw If2 at angle (90+Φ) from If1, where Φ
is the phase angle of current from
voltage. If current is leading, take the angle
of If2 as (90-Φ).
5.
Find the resultant field current, If and mark its magnitude
on the field current
axis.
6.
From OCC. find the voltage corresponding to If, which will be
E0.
3) ZPF method (Potier method)
Conduct
tests to find I) OCC (upto 125% of rated voltage) II) SCC (for rated current)
III) ZPF (for rated current and rated voltage) IV) Armature Resistance (if
required)
Steps:
1.
By suitable tests plot OCC and SCC
2.
Draw tangent to OCC (air gap line)
3.
Conduct ZPF test at full load for rated voltage and fix the point B.
4.
Draw the line BH with length equal to field current required to produce full
load
current at short circuit.
5.
Draw HD parallel to the air gap line so as to touch the OCC.
6.
Draw DE parallel to voltage axis. Now, DE represents voltage drop IXL and BE
represents the field current required to overcome
the effect of armature reaction.
Triangle BDE is
called Potier triangle and XL is the Potier reactance
7.
Find E from V, IXL
and Φ. Consider Ra also if required. The expression to use is
8.
Find field current corresponding to E.
9.
Draw FG with magnitude equal to BE at angle (90+Ψ) from field current axis,
where Ψ is the phase angle of current from
voltage vector E
(internal phase angle).
10.
The resultant field current is given by OG. Mark this length on field current axis.
11.
From OCC find the corresponding E0.
CONCLUSION:
The
above mentioned methods are indirect methods. Each has it’s own
features.
EMF method is a pessimistic method
because Zs is more than the actual impedance and hence the regulation is more than actual
values.
MMF method gives the voltage
regulation less than the actual value. Therefore it is called Optimistic
method. The voltage regulation is less compared to actual because, the
excitation to overcome armature reaction is determined on unsaturated part of
the saturation curve.
ZPF method gives the voltage
regulation close to the actual value, therefore this is the accurate method.
ASA method gives the actual voltage
regulation because, drop due to saturation effect is also considered so that it
is most accurate method.
Above
all the methods for non salient pole machines and the slip test is for salient
pole machines.
Comments
Post a Comment